Tuesday, 19.03.2024, 11:48
Nova Ice Rink                                                                                                                                                                 
Main Sign Up Login
Welcome, Guest · RSS
Site menu
 
Login form
 
Search
 
Calendar
«  March 2024  »
SuMoTuWeThFrSa
     12
3456789
10111213141516
17181920212223
24252627282930
31
 

 
Statistics

Total online: 1
Guests: 1
Users: 0
 
 Chiller for up to 60 m x 30 m rink
Chiller unit for 60 m x 30 m ice rink or smaller surface

120-400 Ton Air Cooled Series R ™ Chiller 275 ERTAC

R134a - 2 circuits -  3 Screw compressors


Performance
  • Cooling capacity 465.17 kW
  • 1.91 EER (kW/kW) Efficiency
  • Refrigerant charge per circuit R134a 166 kg 91 kg
  • Sound pressure  (A weighted  at 10 m) 68 dBA
  • Note:  Sound pressure measured in accordance with ISO 3746
Evaporator   
  • Type -8 Deg C > LWT >= -12 Deg C
  • Leaving temperature -11.00 C
  • Entering temperature -7.00 C
  • Flow rate 37.22 L/s
  • Pressure drop 113.9 kPa
  • Fouling Factor 0.044000 m2-deg C/kW
  • Ethylene Glycol Fluid type
  • Antifreeze concentration in weight 40.00 %
  • Fluid freezing point -23.8 °C
Condenser
  • Ambient temperature 35.00 C
  • Elevation 0.0 m
  • Fin type Aluminium Fins
  • Ambient Standard Ambient
  • Fan motor Standard Condenser Fans
  • Fan motor power 27.70 kW
  • Number of fans 16
  • Total condenser air flow 68.52 m³/s
Electrical
  • Power voltage 400V/50Hz/3Ph
  • Unit power 243.90 kW
  • Compressor power input 220.00 kW
  • Max Amps 763.00 A 
  • Unit starting current 754.00 A
General Data
  • Length 9138 mm
  • Width 2250 mm
  • Height 2570 mm
  • Shipping weight 8522 kg
  • Operating weight 8745 kg

Copyright MyCorp © 2024